Function of UA 410 D
16
Firmware V1.40 - Doku 2.1 06. April 2016
4.1.1
Required and optional sensors
Temperature sensors used with the UA 410 D may be either required or optional depending on the set controller
type and operating mode. If required sensors are not connected, alarm is always generated in a sensor break.
With optional sensors, alarm is only generated when the sensors are included in sensor scan. Sensor scan
takes place automatically on first start of the controller. The number of scanned sensors can be checked under
menu item 6-1 or with the PC software LDSWin. In this way unconnected sensors can removed from the monito
ring.
Required and optional sensors are listed below:
Controller type
Sensors necessary
for regulation
Optional sensors
(advanced functions)
Single-zone operation
UA 111 X
UA 111 XP
R2.1
R2.2 R2.3 R2.4 R2.5 R2.6 R2.7 R2.8 R4.1
UR 141
R1.1 R4.1
R1.2 R1.3 R1.4 R4.2 R4.3 R4.4
Two-zone operation
UA 111 X
UA 111 XP
R2.1 R2.8
R2.2 R2.3 R2.4 R2.5 R2.6 R2.7 R4.1 R4.8
UR 141
R1.1 R1.3 R4.1 R4.3
R1.2 R1.3 R1.4 R4.2 R4.4
Sensor identification
Legend: Ry.x
y = Sensor type
1
Defrost sensor (evaporator sensor)
2
Supply air sensor
4
Return air sensor/room air sensor
x = Sensor number
1..8
Case part 1..8
Sensor break alarm
Alarm (sensor break) is always generated if required sensors are not connected. If optional sensors are not con
nected, alarm is only generated when the sensors are included by sensor scan. Sensors scan can be initiated
from the menu 6-1 using the parameter
No. Sensors
.
Summary of Contents for UA 410 D
Page 8: ...vi Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 22: ...Application of UA 410 D 14 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 74: ...Pin and Terminal Assignments of UA 410 D 66 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 84: ...Operation of UA 410 D 76 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 132: ...Decommissioning and disposal 124 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 140: ...Specifications of UA 410 D 132 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 142: ...Order numbers and accessories of UA 410 D 134 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...