Menu structure UA 410 D
Contr. type UA 111 X
90
Firmware V1.40 - Doku 2.1 06. April 2016
S
Menu 6-2-1 Type and Version
VERSION
POS: XXXXX
Entry
Default
Ctrlr. Type
XXXXXXX
Set by DIP switch S3
-
UA111X
Software Vers.:
XXXX
Software version of case/coldroom controller
-
Serial No.:
XXXXXX
Device No. of case/coldroom controller
-
S
Menu 6-2-2 Temp. Display
DISPLAY
POS: XXXXX
Entry
Default
Offset
XX K
Offset for temperature display
-10..10
0K
S
Menu 6-2-3 Alarm Delay
ALARMDELAY
POS: XXXXX
Entry
Default
Sensor Fault
XX m
Sensor break alarm delay
0..30
15 min
High/Low Temp.
XX m
High/low temperature alarm delay
0..120
60 min
No Defrost
XX h
No defrost alarm delay
--, 2..168
24 h
Selfholding
X
Alarm self-hold with manual alarm cancellation (YES) or
automatic cancellation on send (NO)
↑
,
↓
,
(Y/N)
N
S
Menu 6-2-4 230V Inputs
Only trained personnel should be allowed to change inputs, as changes may affect other functions.
230V INPUT
POS: XXXXX
Entry
Default
Input1:STORE LIGHT
Function of Digital Input 1 D11/D12 -
Store lighting (2/3)
-
STORE LIGHT
Input2:SETP.TOG.
Function of Digital Input 2 D21/D22 -
Setpoint toggle
-
SETP.TOG.
Input3:LIGHT SWITCH
Function of Digital Input 3 D31/D32 -
Lighting switch (manual case switch)
-
LIGHT SWITCH
Summary of Contents for UA 410 D
Page 8: ...vi Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 22: ...Application of UA 410 D 14 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 74: ...Pin and Terminal Assignments of UA 410 D 66 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 84: ...Operation of UA 410 D 76 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 132: ...Decommissioning and disposal 124 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 140: ...Specifications of UA 410 D 132 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 142: ...Order numbers and accessories of UA 410 D 134 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...