Alarms and Messages of UA 410 D
126
Firmware V1.40 - Doku 2.1 06. April 2016
No.
Message
Cause
Correction
Messages
128
Sensor Fault
Sensor disconnected, short circuiting of sensor. Tem
perature on sensor outside set measuring range. Re
quired or optional sensors are monitored when detec
ted by controller through sensor scan.
Check connecting cable,
check cable screening,
replace sensors affected
134
Safety loop
Not used.
-
135
Oil press.fault1
Not used.
-
136
Oil press.fault2
Not used.
-
189
Refrig. Pt. Disabl.
Refrigeration point enabling disabled.
-
240
Setpoint Change
Setpoint changed.
-
10.1 Alarms and monitoring
10.1.1 Open coldroom door alarm (controller type UR 141)
10.1.2 High or low temperature alarm
High or low temperature is alarmed when temperature rises or falls to the alarm setpoint on the supply air sen
sors (UA 111 X / UA 111 XP) or room air sensors (UR 141) and the set delay has expired.
LOW
T
E
MP
ERA
T
URE
RE
F
ERE
N
CE
V
A
L
UE
A
L
AR
M O
N
A
L
AR
M OFF
°
C
t
d
d
T
E
MP
ERA
T
URE
d =
DE
L
AY
T
IM
E
O
V
ER
T
E
MP
ERA
T
URE
Z
N
R
.
51203
5
86
30
E0
The high temperature setpoint is entered in
°
C, whereas the low temperature setpoint is entered as a difference
to the cooling setpoint in K. High and low temperature setpoints can be set separately for each temperature
zone. The time delay applies to all.
This alarm is inactive during defrosting. Any delay that may have started is reset at the commencement of de
frosting and restarts from the beginning on completion of defrosting.
Summary of Contents for UA 410 D
Page 8: ...vi Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 22: ...Application of UA 410 D 14 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 74: ...Pin and Terminal Assignments of UA 410 D 66 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 84: ...Operation of UA 410 D 76 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 132: ...Decommissioning and disposal 124 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 140: ...Specifications of UA 410 D 132 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 142: ...Order numbers and accessories of UA 410 D 134 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...