Menu structure UA 410 D
Controller type UR 141
116
Firmware V1.40 - Doku 2.1 06. April 2016
S
Menu 2-4-3 Zone 1A Altern.
ALARM 1A
POS: XXXXX
Entry
Default
High Temp Setp
XX °C
High temperature setpoint at which
High Temperature
alarm
is generated
-30..30
-12 °C
Low Temp Setp.
XX K
Low temperature setpoint (difference below temperature
control setpoint) at which
Low Temperature
alarm is gene
rated
--, 0..6
2 K
S
Menu 2-4-4 Zone 2A Altern.
ALARM 2A
POS: XXXXX
Entry
Default
High Temp Setp
XX °C
High temperature setpoint at which
High Temperature
alarm
is generated
-30..30
10 °C
Low Temp Setp.
XX K
Low temperature setpoint (difference below temperature
control setpoint) at which
Low Temperature
alarm is gene
rated
--, 0..6
2 K
8.3.4
Menu 3 Clock
CLOCK
POS: XXXXX
1 Current Time
Move to menu 3-1
2 Defrost timer
Move to menu 3-2
3 Toggle Setpoints
Move to menu 3-3
S
Menu 3-1 Current Time
When connected to the CAN bus, the default time is provided via the time master (store computer,
operator terminal). Any entry made will then be overwritten by the default value.
CLOCK
POS: XXXXX
Entry
Default
Date: XX dd.mm.yy
Display and enter current weekday, date
dd.mm.yy
Time: hh.mm
Display and enter current time
hh.mm
Daylight Saving
X
Display and enter automatic daylight saving change (Y/N)
↑
,
↓
, (Y/N)
Y
Summary of Contents for UA 410 D
Page 8: ...vi Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 22: ...Application of UA 410 D 14 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 74: ...Pin and Terminal Assignments of UA 410 D 66 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 84: ...Operation of UA 410 D 76 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 132: ...Decommissioning and disposal 124 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 140: ...Specifications of UA 410 D 132 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 142: ...Order numbers and accessories of UA 410 D 134 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...