Pin and Terminal Assignments of UA 410 D
62
Firmware V1.40 - Doku 2.1 06. April 2016
6.8
Terminal assignment of the 24 V DC transistor outputs
Warning - hazardous electrical voltage!
Connecting mains power to the transistor outputs will lead
to the destruction of the controller!
Destruction of the transistor outputs!
Due to the capacity of the transistor outputs of
a max. of 50 mA, 24 V DC coupling relays must be used for controlling the load.
ZNG: 113 030 DEF3
Z11
Z12
Z21
Z22
Z31
Z32
Z41
Z42
Z51
Z52
Z61
Z62
Z71
Z72
Z81
Z82
Z91
Z92
Z01
Z02
DISPLAY
2
1
3
5
4
6
12
11
13 14
82
81
83
92
91
93
+24 V DC
AIN1
GND
AIN2
+ 24 V DC
OUT
GND
+ 24 V DC
OUT
SHIELD
82
81
83
92
91
93
24 V DC /
max. 50 mA
USB
L
EDs
Controller
Type
Digital output 1
81: 24 V DC / max. 50 mA
82: OUT
83: GND
Digital output 2
91: 24 V DC / max. 50 mA
92: OUT
93: SHIELD
UA 111
Case lighting
Without function
UA 111 XP
Without function
Without function
UA 141
Without function
Without function
If any transistor output is activated by the controller, the associated green LED lights,
see chapter 5.5.1 "Status LEDs" for details.
For further details on the function of the transistor outputs see chapter 6.4.
Summary of Contents for UA 410 D
Page 8: ...vi Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 22: ...Application of UA 410 D 14 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 74: ...Pin and Terminal Assignments of UA 410 D 66 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 84: ...Operation of UA 410 D 76 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 132: ...Decommissioning and disposal 124 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 140: ...Specifications of UA 410 D 132 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...
Page 142: ...Order numbers and accessories of UA 410 D 134 Firmware V1 40 Doku 2 1 06 April 2016 Notice ...