172
Typ EP 501
PROFIBUS DP
26.
DESCRIPTION OF THE PROFIBUS DP
26.1. Technical data
The protocol sequence complies with the standard DIN 19245 Part 3.
GSD.file
BUER0C1E.gsd
Bitmap.files
BUER0C1E.bmp
PNO-ID.
0C1E Hex
Baud.rate
Max. 12 mbaud
(is automatically set by the device)
Sync.and.Freeze.mode
Are not supported
Diagnosis.telegram
No device-specific diagnosis
Parameter.telegram
No user parameters
The process data is configured in the device and in the PROFIBUS master.
Maximum 10 process values (total
INPUT
and
OUTPUT
) can be transferred.
26.2. Interfaces
Binary input
24 V DC
Type.EP.501
PROFIBUS DP
Inputs
Outputs
Supply
Operation
Bus
Bus
Figure 106: Interfaces PROFIBUS DP
english