145
Typ EP 501
Auxiliary functions
Key
Action
Description
/
Increase value
<
Changing the decimal
place
Input upper temperature limit
TEMP.MAX
.
OK
Press
Acknowledge value.
/
Select
TEMP.MIN
INPUT
Press
Open factory setting for lower temperature limit.
/
Increase value
<
Changing the decimal
place
Input lower temperature limit
TEMP.MIN
.
OK
Press
Acknowledge value.
EXIT
Press
Return to the
TEMP.CHECK
menu.
EXIT
Press
Return to the
DIAGNOSE
main menu.
Table 82:
TEMP.CHECK; specifying temperature limit.
STROKE.CHECK
–.End.position.monitor
The
STROKE.CHECK
function is used to monitor the physical end positions of the armature. In this way wear marks
can be detected on the valve seat.
To do this, a tolerance band is specified for the lower end position (position 0 %) and for the upper end position
(position 100 %). If an end position exceeds or falls below the tolerance band, a message is output.
• To do this, a history entry is made in the
HISTORY
submenu. For description see “24.2.22.7. History entries in
• The status signal, which is assigned to the message, is indicated at short intervals on the display.
See also
D.MSG
and
CONFIG.MSG
in Chapter “24.2.22.5”, page 133.
In addition to the monitor there is an end position slave pointer. This indicates the minimum and maximum position
of the determined end positions. The slave pointer can be reset by pressing the
CLEAR
key.
Display.
STROKE.CHECK
Description.of.the.functions
EXIT
29-9-1
STROKE.CHECK
MAX
MIN
LIMIT
HISTORY
30. 9 %
67.6.%
MAX
indicates the maximum position of the slave pointer
MIN
indicates the minimum position of the slave pointer
The tolerance band for the physical end positions can be set in the
LIMIT
submenu. A message is output if the temperature goes outside the per-
mitted range.
Example:
Input upper end position
TOL MAX
= 1 %
If the position is less than -1 %, a message is output
Input lower end position
TOL ZERO
= 1 %
If the position is greater than 101 %, a message is output
The history entries of the last 3 messages can be viewed and deleted in
the
HISTORY
submenu.
Table 83:
STROKE.CHECK; end position monitor
english