180
Typ EP 501
PROFIBUS DP
28.4. Configuration via the control (PROFIBUS DP
Master)
The configuration requires the following components:
• Software suitable for the configuration. For example Step7 from Siemens A brief description of this can be
found in the following chapter “28.5. Configuration with Siemens Step7”.
• GSD file (download from the EBRO homepage:)
28.4.1. Supplementary literature on the configuration of the
PROFIBUS DP
More detailed information can be found in the supplementary instructions on the EBRO homepage:
• „Configuration on the PROFIBUS by means of GSD file“
28.4.2. Configuration of the process values
→
The PDI (Process Data Input) input first.
PDI
:
Process.Data.Input
(from the Type EP 501 to the controller)
Name
Description
Identifier
PDI:POS
Actual position (position)
Actual value of positioner as ‰. Value range 0 – 1000.
Values < 0 or > 1000 are possible if e.g. Autotune has not run
through correctly.
GSD file:
PDI:POS
Identifier (HEX): 41, 40, 00
PDI:CMD
Nominal position (command)
Set-point value of positioner as ‰. Value range 0 – 1000.
GSD file:
PDI:CMD
Identifier (HEX): 41, 40, 01
PDI:TEMP
Device temperature (temperature)
Temperature of 0.1 °C is measured on the CPU board by the
sensor,
Value range -550 (-55 °C) – +1250 (+125 °C)
GSD file:
PDI:TEMP
Identifier (HEX): 41, 40, 04
PDI:MODE
Operating state (operation mode)
Operating state:
GSD file:
PDI:MODE
0:
AUTO
1:
MANU
2:
XTUNE
12:
BUSSAFEPOS
Identifier (HEX): 41, 00, 05
english