141
Typ EP 501
Auxiliary functions
TRAVEL.ACCU
–.Path.accumulator
The path accumulator records and adds up the path which the actuator piston covers. A movement of the
actuator piston is detected when the position changes by at least 1 %.
The interval for outputting messages is specified by inputting a limit for the total number of piston movements.
• To do this, a history entry is made in the
HISTORY
submenu. For description see “24.2.22.7. History entries in
• The status signal, which is assigned to the message, is indicated at short intervals on the display.
See also
D.MSG
and
CONFIG.MSG
in Chapter “24.2.22.5”, page 133.
Display.
TRAVEL.ACCU
Description.of.the.functions
EXIT
INPUT
29-6-1
TRAVEL.ACCU
STROKE
LIMIT
NEXT.M
HISTORY
1000000 cm
999954 cm
20.0.mm
The
STROKE
submenu specifies the total stroke of the actuator piston. The
total stroke is automatically determined during the basic setting of the device
(running
X.TUNE)
.
In the case of an analog position sensor, the total stroke must be input by
pressing the
INPUT
key.
The interval for outputting the message can be changed in the
LIMIT
submenu. A piston movement which covers 10 km has been preset at the
factory.
After
NEXT.M
the remaining piston movement distance is displayed until the
next message appears.
The history entries of the last 3 messages can be viewed and deleted in the
HISTORY
submenu.
Table 77:
TRAVEL.ACCU; path accumulator
Operating structure:
ENTER
INPUT
INPUT
ENTER
OK
OK
ESC
ESC
EXIT
CLEAR
Input
Limit
Input total
stroke
*
History entry
is displayed
Display the remaining distance until the next message
TRAVEL.ACCU
LIMIT
STROKE
NEXT M.
HISTORY
Delete.history.entry
EXIT
*
Input required for analog position sensor only
Figure 84:
Operating structure TRAVEL.ACCU
english