PXG 900 User's Guide - Firmware Version 4.3 - 1/9/2017
67
47808
BACnet/IP
UDP
161
SNMP
UDP
162
SNMP
UDP
The following ports are open and necessary for proper PXG operation:
Port Number
Protocol/Use
TCP/UDP
7011
Eaton's Mercury Websockets
TCP
7012
Eaton's Mercury Websockets – Secure via TLS
TCP
8181
Eaton's Mercury for communications with PXI Software
TCP
8443
Eaton's Mercury – Secure via TLS for communications with PXI Software
TCP
These ports cannot be disabled or their port numbers changed.
Browser Specific Notes
If you use HTTPS with Internet Explorer 10 you must enable TLS version 1.2 support in the browser. The
PXG does not support SSL version 3.
Restart your browser after loading the certificate to avoid any problems caused by the browser caching data.
Settings
Network Access Tab - Controlling Access to Various Protocol Servers
BACnet/IP
Under BACnet/IP, you should only enable those services that you will be using. Leave everything else disabled. For
those services that you do enable, make sure that you also enable Trusted Hosts for each and then maintain the
minimum number of trusted hostnames/IP addresses that you need. Note that you must have Trusted Hosts
enabled in order to save any trusted host machine names/IP addresses you've added.
Modbus TCP Server Configuration
Unless you have a specific need to enable Write Commands, make sure that this is Disabled.
SNMP
Unless you require SNMP features, it is recommended that you leave the overall support turned off by unchecking
SNMP support in the Access Control section of the Network Access tab. If you require SNMP support, v1 and v3
features are independently configurable.
Summary of Contents for PXG 900
Page 1: ...PXG 900 User s Guide Power Xpert Gateway 900 ...
Page 14: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 12 Adding an IQ 250 ...
Page 16: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 14 Adding a Digitrip 1150 ...
Page 18: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 16 Adding a BIM II ...
Page 21: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 19 Locale Settings ...
Page 40: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 38 Audit Logs ...
Page 53: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 51 Device Details ...