PXG 900 User's Guide - Firmware Version 4.3 - 1/9/2017
11
1.
2.
3.
4.
5.
6.
7.
8.
9.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Initial Setup
The PXG helps you when adding devices, guiding you through the initial setup steps:To add either a Modbus RTU
or INCOM device:
Choose Edit.
Choose Add Device under the appropriate port.
In the sidebar, select the device type under Family.
Select the Model Series.
Select the device Model.
Enter a meaningful name for the device.
Enter the device address: 1-247 decimal for Modbus, 1-FFE hexadecimal for INCOM. If you enter an address
that's already in use, the box outline will turn red and you won't be able to save the device configuration until
you select a unique address.
If Enable Waveforms is available, decide whether you wish to have the PXG capture these.
Choose Save Device Configuration.
The following examples assume that the devices are on the appropriate networks and that the ports are properly
configured.
Example 1: Adding An IQ 250 Meter
Connect the IQ 250 Meter to either COM1 or COM2.
Choose the Network tab.
Choose Edit.
Choose Add Device under the appropriate COM port column.
Select Meters under Family.
Select IQ 200 Series under Model Series.
Select IQ250 under Model.
Enter a name, such as "IQ250_1" under Name.
Set the Serial Address (1-247 decimal) to match the address you set on the meter.
Choose Save Device Configuration.
Choose Edit.
Summary of Contents for PXG 900
Page 1: ...PXG 900 User s Guide Power Xpert Gateway 900 ...
Page 14: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 12 Adding an IQ 250 ...
Page 16: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 14 Adding a Digitrip 1150 ...
Page 18: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 16 Adding a BIM II ...
Page 21: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 19 Locale Settings ...
Page 40: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 38 Audit Logs ...
Page 53: ...PXG 900 User s Guide Firmware Version 4 3 1 9 2017 51 Device Details ...