112
CANopen external communication cards
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Status word
The Status Word provides drive status for the current control. By default this is
mapped into the first 2 bytes of txPDO1
Table 145. 0x6041 status word
Bit
Name
Description
0
Ready to Switch ON
Device is in the ready state, ready to switch on
1
Switched ON
Device switch is enabled
2
Operation Enabled
Device drive is enabled and running
3
Fault Present
Device Fault is present
4
voltage disable
Drive output voltage is enabled
5
Quick Stop
Device Quick Stop is enabled
6
Switching On Disable
Device switch is disabled
7
Warning Present
Indicates if drive is in Warning state
8
Manufacturer Specific
Not Used
9
Remote
Indicates if the drive is in the Remote control state
10
Target Reached Or Exceeded
Target velocity is reached
11
Manufacturer Specific
Not Used
12
Manufacturer Specific
Not Used
13
Manufacturer Specific
Not Used
14
Manufacturer Specific
Not Used
15
Manufacturer Specific
Not Used
VL Target velocity
The signed value of the requested motor rpm speed. When the value is reading
negative, it indicates the motor spinning in the counterclockwise direction. By
default, this is mapped into the bytes of RxPDO1.
Range: –32768 to 32767
VL Velocity demand
The signed value is of the ramp generator output scaled into rpm and is a read only
value. A negative value will indicate the motor is running in the clockwise direction.
Range: –32768 to 32767
VL Velocity control effort
This signed value is the motor actual rpm speed. A negative value will indicate that the
motor is running in the clockwise rotation. By default, this is mapped into the TxPDO1.
Range: –32678 to 32767