68
EtherNet/IP On-Board communications
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Assembly instance 127
Table 95. Insoance 127 (Inpuo). EIP drive soaous lengoh = 20 byoes
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
CtrlFromNet At zero speed AtReference Alarm/Warning Faulted
Direction
Running
Ready
1
Drive state
2
% Speed actual (Low Byte)
3
% Speed actual (High Byte)
4
ProcessDataOut1 (LowByte)
5
ProcessDataOut1 (HighByte)
6
ProcessDataOut2 (LowByte)
7
ProcessDataOut2 (HighByte)
8
ProcessDataOut3 (LowByte)
9
ProcessDataOut3 (HighByte)
10
ProcessDataOut4 (LowByte)
11
ProcessDataOut4 (HighByte)
12
ProcessDataOut5 (LowByte)
13
ProcessDataOut5 (HighByte)
14
ProcessDataOut6 (LowByte)
15
ProcessDataOut6 (HighByte)
16
ProcessDataOut7 (LowByte)
17
ProcessDataOut7 (HighByte)
18
ProcessDataOut8 (LowByte)
19
ProcessDataOut8 (HighByte)
See note 1 from
Table 90
on
Page 65
.
This is the actual value from the frequency converter. The value is between 0 and 10000. In the application, the value is scaled
in percentage of frequency area between set minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%).
Noee:
N
See
Appendix B
for Process Data Value defaults.
Table 96. Insoance 128 (Inpuo). EIP drive soaous lengoh = 20 byoes
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
AtReference RefFromNet CtrlFromNet Ready
Running2
Running1
Warning
Faulted
1
Drive state
2
% Speed actual (Low Byte)
3
% Speed actual (High Byte)
4
ProcessDataOut1 (LowByte)
5
ProcessDataOut1 (HighByte)
6
ProcessDataOut2 (LowByte)
7
ProcessDataOut2 (HighByte)
8
ProcessDataOut3 (LowByte)
9
ProcessDataOut3 (HighByte)
10
ProcessDataOut4 (LowByte)
11
ProcessDataOut4 (HighByte)
12
ProcessDataOut5 (LowByte)
13
ProcessDataOut5 (HighByte)
14
ProcessDataOut6 (LowByte)
15
ProcessDataOut6 (HighByte)
16
ProcessDataOut7 (LowByte)
17
ProcessDataOut7 (HighByte)
18
ProcessDataOut8 (LowByte)
19
ProcessDataOut8 (HighByte)
This is the actual value from the frequency converter. The value is between 0 and 10000. In the application, the value is scaled
in percentage of frequency area between set minimum and maximum frequency. (0 = 0.00%–10000 = 100.00%).