DeviceNet external communication cards
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Assembly instance 127
Table 172. Instance 127 (Input). EIP Drive status length = 20 bytes
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
CtrlFromNet
At Zero Speed
At Reference
Alarm/Warning
Faulted
Direction
Running
Ready
1
NA
2
% Speed Actual (Low Byte)
3
% Speed Actual (High Byte)
4
ProcessDataOut1 (LowByte)
5
ProcessDataOut1 (HighByte)
6
ProcessDataOut2 (LowByte)
7
ProcessDataOut2 (HighByte)
8
ProcessDataOut3 (LowByte)
9
ProcessDataOut3 (HighByte)
10
ProcessDataOut4 (LowByte)
11
ProcessDataOut4 (HighByte)
12
ProcessDataOut5 (LowByte)
13
ProcessDataOut5 (HighByte)
14
ProcessDataOut6 (LowByte)
15
ProcessDataOut6 (HighByte)
16
ProcessDataOut7 (LowByte)
17
ProcessDataOut7 (HighByte)
18
ProcessDataOut8 (LowByte)
19
ProcessDataOut8 (HighByte)
This is the actual value from the frequency converter. The value is between 0 and 10000. In the
application, the value is scaled in percentage of frequency area between set minimum and maximum
frequency. (0 = 0.00%–10000 = 100.00%).
otee:
N
See
Appendix B
for Process Data Value defaults.