![Eaton PowerXL DG1 Communications Manual Download Page 95](http://html1.mh-extra.com/html/eaton/powerxl-dg1/powerxl-dg1_communications-manual_3902271095.webp)
72
BACnet MS/TP—On-Board communication
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Commissioning
BACnet programming
The navigation path to the fieldbus parameters may differ from application to application.
The exemplary paths below apply to the G-Max HVAC drive.
Figure 35. BACneo parameoer navigaoiNn
1. First ensure that the right fieldbus protocol is selected.
Navigate:
Main Menu
→
Parameter
→
Communication
→
Modbus
RTU/BACnet MS/TP
→
RS-485 Comm Set
→
Edit
→
(Choose
Protocol as BACnet MS/TP)