![Eaton PowerXL DG1 Communications Manual Download Page 26](http://html1.mh-extra.com/html/eaton/powerxl-dg1/powerxl-dg1_communications-manual_3902271026.webp)
3
Option card slots
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Option card slots
The control board is located inside the control unit of the
DG1 Series Drive. There are two slots, labeled A and B,
on the control board. The different option boards can be
added to any slots. For more information see “PowerXL
DG1 Option Board Summary.” When the DG1 Series Drive
is assembled at the factory, no option boards are installed
in slots A and B. If an incorrect board is plugged into either
slot, the board will not work, but there is no danger to
personal or for equipment damage.
Figure 3. DG1 series control board location
Connect DSP Part
to Power Board
Keypad
Connect MCU Part
to Power Board
Battery (Standard)
RJ45 EtherNet/IP,
Modbus TCP
Optional Card A
Optional Card B
RS-485 Termination
Resistor
Removable
MOV Screw
Motor Ground
Clamp Location
Grounding
Strap Location
Grounding
Strap Location
Line Ground
Clamp Location
Removable
EMC Screw
Control I/O
Terminals
AI Mode Selection
STO
Fan Power Wire
Line Side
Motor
ON
12
3
ON
1
Figure 4. Drive control board layout showing option