CANopen external communication cards
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Fixed control word
Table 147. Fixed control word
Bit
Name
0
Run
1
Counterclockwise
2
Rising edge of this bit will reset active fault
3
FB Input data 1
4
FB Input data 2
5
FB Input data 3
6
FB Input data 4
7
Bypass
8
FB_Ctrl
9
FB_Ref
10
Not in use
11
Not in use
12
Not in use
13
Not in use
14
Not in use
15
Not in use
Bit
Description
Value = 0
Value = 1
0
Stop
RUN
1
Clockwise
Counterclockwise
2
Rising edge of this bit will reset active fault
Rising edge of this bit will reset active fault
3
FB Input data 1 off
FB Input data 1 On
4
FB Input data 2 off
FB Input data 2 On
5
FB Input data 3 off
FB Input data 3 On
6
FB Input data 4 off
FB Input data 4 On
7
Switch to drive
Switch to bypass
8
Control of drive is not selected from fieldbus
Control of drive is selected from fieldbus
9
Reference is not selected from fieldbus
Reference is selected from fieldbus
10–15
Not in use
Not in use
Speed ref percentage
The Speed Reference Percentage is based off a 0 to 100.00 %(10000) scale with
0 being 0 rpm and 10000 indicating 100.00% speed value. A negative value will
indicate the inverted direction.
Process data in
The Process Data In values are based off the application selected. See
Appendix B
to reference the current Process Data In values assigned.