19
Modbus TCP On-Board communications
POWERXL DG1 SERIES VFD
MN040010EN—September 2016 www.eaton.com
Commissioning
Connections and wiring
The Ethernet port supports 10/100 Mb speeds in both
full and half-duplex modes. The boards must be connected
to the Ethernet network with a shielded CAT-5e cable.
A crossover cable (at least CAT-5e cable with STP, shielded
twisted pair) may be needed if you want to connect the
EtherNet/IP board directly to the master appliance.
Use only industrial standard components in the network
and avoid complex structures to minimize the length of
response time and the amount of incorrect dispatches.
It is often a good practice to use a subnet that is different
from other devices not related to the drive control.
Figure 12. CAT-5e cable
Figure 13. Keypad navigation to ethernet comm settings
In this menu you will be able to scroll through the below
settings to setup the communication protocol.
Table 38. EtherNet/IP / Modbus TCP—P20.3
Code
Parameter
Min.
Max.
Unit
Default
ID
Note
P20.3.1
IP Address Mode
1
1500
0 = Static IP
1 = DHCP with AutoIP
P20.3.2
Active IP Address
1507
P20.3.3
Active Subnet Mask
1509
P20.3.4
Active Default Gateway
1511
P20.3.5
MAC Address
1513