UPS INSTALLATION PLAN AND UNPACKING
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
3-24
Terminals E1 through E11 are 2‐hole busbar mountings for standard NEMA 2‐hole
barrel lugs. The power wiring connections for this equipment are rated at 90
°
C. See
Table 3‐17 for power cable terminations, Table 3‐18 for supplied terminal hardware,
and Table 3‐19 for recommended installation parts and tools not supplied by Eaton.
Figure 4‐17 through Figure 4‐20 show the location of the power cable terminals inside
the UPS.
Table 3‐17. UPS External Power Cable Terminations for Three/Four UPM Models
Terminal Function
Terminal
Function
Bus Landings
(using both sides of bus)
Tightening Torque
Nm (lb ft)
Bolt Size
AC Input to UPS Rectifier
E1
Phase A
6 – 2 bolt mounting
76 (56)
M12
E2
Phase B
6 – 2 bolt mounting
76 (56)
M12
E3
Phase C
6 – 2 bolt mounting
76 (56)
M12
AC Input to Bypass
E6
Phase A
6 – 2 bolt mounting
76 (56)
M12
E7
Phase B
6 – 2 bolt mounting
76 (56)
M12
E8
Phase C
6 – 2 bolt mounting
76 (56)
M12
AC Output to Critical Load
E9
Phase A
6 – 2 bolt mounting
76 (56)
M12
E10
Phase B
6 – 2 bolt mounting
76 (56)
M12
E11
Phase C
6 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Common
Battery
E4
Battery (+)
16 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
16 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 1)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 2)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 3)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or Battery
Disconnect to UPS – Separate
Battery (UPM 4 FI-UPM)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
Input and Output Neutral
E12
Neutral
12 – 2 bolt mounting
76 (56)
M12
Customer Ground
Ground
Ground
15 – 2 bolt mounting
76 (56)
M12
NOTE
NOTE
Bypass terminations are not applicable to IOM configurations.