UPS INSTALLATION PLAN AND UNPACKING
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
3-17
Table 3‐9. 415V Input/Output Ratings and External Wiring Requirements for the Three/Four UPM Models – Common Battery
Basic Unit Rating
Units
Rating
50/60
Hz
Rating
50/60
Hz
Rating
50/60
Hz
Rating
50/60
Hz
Rating
50/60
Hz
Rating
50/60
Hz
kVA
kW
675
675
750
750
825
825
900
900
1000
1000
1100
1100
Input and Output Voltage
Volts
415/415
415/415
415/415
415/415
415/415
415/415
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
A
Amps
1156
1284
1412
1541
1712
1883
AWG or
kcmil
(each)
500
(5)
500
(6)
500
(6)
500
(6)
500
(8)
500
(8)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
939
1043
1148
1252
1391
1530
Minimum Conductor Size
Number per Phase
AWG or
kcmil
(each)
500
(4)
500
(5)
500
(5)
500
(5)
500
(6)
500
(6)
DC Input from Battery Disconnect to UPS
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
(1) Positive, (1) Negative
C
Total
Amps
1480
1645
1809
1974
2193
2412
AWG or
kcmil
(each)
500
(6)
500
(8)
500
(8)
500
(8)
500
(9)
500
(12)
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps
939
1043
1148
1252
1391
1530
Minimum Conductor Size
Number per Phase
AWG or
kcmil
(each)
500
(4)
500
(5)
500
(5)
500
(5)
500
(6)
500
(6)
NOTE
Callout letters
A
,
B
,
C
, and
D
NOTE
Bypass wiring data is not applicable to IOM configurations.
Battery Conductor Sizing:
Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system
performance and battery run time.
Battery Cable Routing Requirements
Conduit applications:
* Each conduit must have a Positive, Negative, and Ground conductor.
* There must be an equal number of positive and negative conductors in a single conduit. Only one ground conductor is required in each
conduit.
Raceway applications:
* Positive and negative battery cables must be run side by side in the raceway in an alternating pattern (+ - + - + - + -).
* There must be a ground cable running in the raceway with the battery cables
.