PRODUCT SPECIFICATIONS
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
10-3
10.2.3
UPS Environmental
Operating Temperature
All ratings except 1200 kW, 900 kW : 0 to 40°C (32 to 104°F) at
elevation up to 1000m without derating.
For 1200 kW, 900 kW : 0 to 35°C at elevation up to 1000m without
derating.
The recommended operating temperature is 25°C (77°F).
Operating Altitude
Maximum 1000m (3300 ft) at 40°C without derating
Storage Temperature
–25 to +60°C, excluding batteries (prolonged storage above 40°C
causes rapid battery self‐discharge)
Relative Humidity (Operating and
Storage)
5% to 95% maximum noncondensing
Acoustical Noise
83 dB at a 1m distance, A weighted for three UPM UPS
85 dB at a 1m distance, A weighted for four UPM UPS
EMI Suppression
Meets IEC 62040-2, category C3
Electrostatic Discharge (ESD)
Immunity
Meets IEC 801‐2 specifications. Withstands up to 25 kV pulse
without damage and with no disturbance or adverse effect to the
critical load.