![Eaton Power Xpert 9395P-1200 Installation And Operation Manual Download Page 60](http://html1.mh-extra.com/html/eaton/power-xpert-9395p-1200/power-xpert-9395p-1200_installation-and-operation-manual_4265912060.webp)
UPS INSTALLATION PLAN AND UNPACKING
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
3-34
2.
Use a forklift or pallet jack to move the packaged cabinets to the installation site,
or as close as possible, before unpacking. If possible, move the cabinets using
the pallet. Insert the forklift or pallet jack forks from the right side of the pallet
(facing the cabinet), between the supports on the bottom of the pallet (see
Figure 3‐9 to Figure 3‐11 for the UPS cabinet center of gravity measurements). If
the cabinets must be moved using the cabinet front or rear fork lift slots, see the
caution statement at the beginning of this procedure.
C
A
U
T
I
O
N
Do not tilt the UPS cabinets more than 10° from vertical or the cabinets may tip over.
MISE EN GARDE!
Ne pas incliner les armoires d’onduleur à plus de 10 degrés de la verticale puisqu’elles pourraient se
renverser.
3.
Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft)
on each side for removing the cabinet from the pallet.
NOTE
The ISBM and UPM sections are shipped with debris shields covering the ventilation grills on top of
the sections (see Figure 4‐15). Do not remove the debris shields until installation is complete.
4.
Remove the protective covering from the cabinets.
5.
Remove the packing material, and discard or recycle in a responsible manner.
6.
Inspect the contents for any evidence of physical damage, and compare each
item with the Bill of Lading. If damage has occurred or shortages are evident,
contact an Eaton service representative immediately to determine the extent of
the damage and its impact on further installation.
NOTE
While waiting for installation, protect the unpacked cabinets from moisture, dust, and other harmful
contaminants. Failure to store and protect the UPS properly may void your warranty.
Summary of Contents for Power Xpert 9395P-1200
Page 195: ......
Page 196: ... P 1640005004 P 164000500 4 ...