UPS INSTALLATION PLAN AND UNPACKING
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
3-20
Table 3‐12. 400V Input/Output Ratings and External Wiring Requirements for the Three/Four UPM Models – Separate Battery
Basic Unit Rating
Units
Rating
50/60
Hz
Rating
50/60
Hz
Rating
50/60
Hz
Rating
50/60
Hz
Rating
50/60
Hz
Rating
50/60
Hz
kVA
kW
675
675
750
750
825
825
900
900
1000
1000
1100
1100
Input and Output Voltage
Volts
400/400
400/400
400/400
400/400
400/400
400/400
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
A
Amps
1199
1332
1465
1599
1776
1954
AWG or
kcmil
(each)
500
(5)
500
(6)
500
(6)
500
(6)
500
(8)
500
(8)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
974
1083
1191
1299
1443
1588
Minimum Conductor Size
Number per Phase
AWG or
kcmil
(each)
500
(5)
500
(5)
500
(5)
500
(6)
500
(6)
500
(6)
DC Input from Each Battery Disconnect to Each UPS UPM
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
C
Amps
per
UPM
603
603
603
603
603
603
AWG or
kcmil
(each)
500
(3)
500
(3)
500
(3)
500
(3)
500
(3)
500
(3)
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps
974
1083
1191
1299
1443
1588
Minimum Conductor Size
Number per Phase
AWG or
kcmil
(each)
500
(5)
500
(5)
500
(5)
500
(6)
500
(6)
500
(6)
NOTE
Callout letters
A
,
B
,
C
, and
D