background image

FALCON

®

ELECTRIC, INC.

SUP Series

TM

User’s Guide

700-1000VA

WWW.FALCONUPS.COM

800.842.6940

SUP700-1C, SUP1.0K-1C

FALCON® ELECTRIC, INC.

Irwindale, CA 91706

Tel. 626-962-7770

Fax. 626 962-7720

OM48031-SUP, 01/09/04, Rev A.

5116 Azusa Canyon Road

Summary of Contents for SUP1.0K-1C

Page 1: ...INC SUP SeriesTM User s Guide 700 1000VA WWW FALCONUPS COM 800 842 6940 SUP700 1C SUP1 0K 1C FALCON ELECTRIC INC Irwindale CA 91706 Tel 626 962 7770 Fax 626 962 7720 OM48031 SUP 01 09 04 Rev A 5116 Az...

Page 2: ...Diagram Description 9 Chapter 4 Operation 11 Turning The UPS On and Off 11 UPS Self Test 11 UPS Overload Condition 11 DC Start Cold Start 11 Green Mode Function 11 Battery Charging 12 UPS Reset 12 Re...

Page 3: ...detergent on the UPS Never attempt to service batteries High voltage exists within the unit which could cause electrical shock Servicing of batteries should be performed or supervised by personnel kno...

Page 4: ...isplay gives immediate and detailed UPS and power information without having to connect an expensive monitoring computer An intelligent RS 232 computer interface port is also located on the UPS rear p...

Page 5: ...50Hz European source verify the connected equipment was designed to operate from a 120Vac 50Hz power source This information is stated on the nameplate label located on the model number label located...

Page 6: ...nd will open when the utility fails Pins 5 and 4 are normally open and will close at the low battery indication The UPS will shut down when a 5 12 Vdc voltage is applied across Pins 6 and 7 for three...

Page 7: ...quid Crystal Display LCD is provided Please reference the number designation for the display function and the function descriptions referenced in this manual Refer to pages 6 8 in this manual C Two LC...

Page 8: ...ode The sinewave symbol will be displayed when the UPS is operating normally from the utility line Battery Mode The sinewave and battery symbols will blink when the UPS is operating on its internal ba...

Page 9: ...0 C the UPS will shutdown to prevent damage due to excessive overheating 9 Fan off This symbol is used on special extended backup models only 10 Alarm off The audible alarm has been silenced To reset...

Page 10: ...ill turn on when the display reaches zero Battery Minutes to off The estimated remaining battery run time while in battery backup mode LCD Metering Display Modes use display scroll buttons to change m...

Page 11: ...t the incoming telephone line to one of the jacks Then connect the fax modem or other device to be protected to the other jack 7 Audible Alarms Reference the following table ALARM PERIOD STATUS INDICA...

Page 12: ...if the overload is removed the UPS will automatically turn on again If the overload is still present the UPS will turn off and stay off requiring the UPS be manually restarted Always correct any over...

Page 13: ...to a loss of utility power 7 UPS Reset In the event the UPS will not accept commands and appears to be locked up depress the control button for and hold for ten seconds The UPS CPU will be reset 8 Re...

Page 14: ...r computer room environments the batteries should be replaced every three to five years Never attempt to service batteries High voltage exists within the unit which could cause electrical shock Servic...

Page 15: ...er s instructions may cause interference to radio and television reception All models covered in this manual have been tested and found to comply with the limits for a Class A computing device in acco...

Page 16: ...rds The RMA number issued must appear on the outside of the shipping carton The original shipping container must be used when returning any SUP Series product Falcon Electric will not assume any respo...

Page 17: ...ng the nature of the trouble experienced and the disposition of the equipment after repair The equipment will be returned freight collect by FALCON to the location specified via the best and least exp...

Page 18: ...dity 10 to 95 Non Condensing Cooling Low Velocity Forced Air Fans Audible Noise 1 meter 45dBA Controls and Indicators Control One Main Control Button UPS On Off Self Test Reset Silence Alarms Selectio...

Reviews: