UPS INSTALLATION PLAN AND UNPACKING
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
3-23
Table 3‐15. UPS Intercabinet Power Cable Terminations for the Three/Four UPM Models
Terminal Function
Terminal
Function
Bus Landing
Tightening Torque
Nm (lb ft)
Stud
AC Input to UPM Section
E1A (UPM 1)
E1A (UPM 2)
E1A (UPM 3)
E1A (UPM 4 – Four UPM Model)
Phase A
4 – stud mounting
14.2 (10.4)
M8
E2A (UPM 1)
E2A (UPM 2)
E2A (UPM 3)
E2A (UPM 4 – Four UPM Model)
Phase B
4 – stud mounting
14.2 (10.4)
M8
E3A (UPM 1)
E3A (UPM 2)
E3A (UPM 3)
E3A (UPM 4 – Four UPM Model)
Phase C
4 – stud mounting
14.2 (10.4)
M8
AC Output from UPM Section
E9A (UPM 1)
E9A (UPM 2)
E9A (UPM 3)
E9A (UPM 4)
Phase A
4 – stud mounting
14.2 (10.4)
M8
E10A (UPM 1)
E10A (UPM 2)
E10A (UPM 3)
E10A (UPM 4)
Phase B
4 – stud mounting
14.2 (10.4)
M8
E11A (UPM 1)
E11A (UPM 2)
E11A (UPM 3)
E11A (UPM 4)
Phase C
4 – stud mounting
14.2 (10.4)
M8
E12A (UPM 1)
E12A (UPM 2)
E12A (UPM 3)
E12A (UPM 4)
Neutral
4 – stud mounting
14.2 (10.4)
M8
DC Input to UPM Section
1E4A (UPM 1)
2E4A (UPM 2)
3E4A (UPM 3)
3E4A (UPM 4)
Positive
6 – stud mounting
(2 per UPM)
14.2 (10.4)
M8
1E5A (UPM 1)
2E5A (UPM 2)
3E5A (UPM 3)
3E5A (UPM 4)
Negative
6 – stud mounting
(2 per UPM)
14.2 (10.4)
M8
Table 3‐16. Supplied Intercabinet Wiring Terminal Hardware Kit
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Flat Washer
M8
36
UPM AC Input, UPM Battery Input, UPM AC
Output
180500036-080
Conical Washer
M8
36
UPM AC Input, UPM Battery Input, UPM AC
Output
180500037-080
Nut
M8
36
UPM AC Input, UPM Battery Input, UPM AC
Output
180200001-05