UPS INSTALLATION PLAN AND UNPACKING
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
3-26
Table 3‐20. 480V Power Cable Conduit Requirements
UPS Model
Voltage
Terminal
Number of
Wires in
Conduit
Minimum
Conduit Trade
Size
Number of
Conduits
Eaton 9395P-1200/1200
Eaton 9395P-1200/1100
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
6
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
5
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
7
4
4
Eaton 9395P-1200/1000
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
5
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
5
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
5
3.5
5
Eaton 9395P-1200/675
Eaton 9395P-1200/750
Eaton 9395P-1200/825
Eaton 9395P-1200/900
See Note 1
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
6
AC Input to Bypass and Output
(A, B, C, Ground)
4
3
5
DC
(Common Battery)
Battery
(Positive, Negative, Ground)
7
4
4
All models
DC
(Separate Battery -
per UPM)
Battery
(Positive, Negative, Ground)
7
4
1
NOTE 1
Because of the future upgradability to a fully rated 1200 kVA UPS with the addition of the FI-UPM, these conduit sizes are specified for an
1200 kVA UPS.
NOTE 2
Bypass conduit data is not applicable to IOM configurations.
Battery Cable Routing:
Refer to the notes at the bottom of Table 3‐5 to Table 3‐14 Input/Output Ratings and External Wiring Requirements
.