UPS INSTALLATION PLAN AND UNPACKING
Eaton Power Xpert 9395P-1200 UPS (1200 kVA, 1200 kW) Installation and Operation Manual
S
P-164000500 Rev 4
www.eaton.com/powerquality
3-22
Table 3‐14. 380V Input/Output Ratings and External Wiring Requirements for the Three/Four UPM Models – Separate Battery
Basic Unit Rating
Units
Rating
50/60
Hz
Rating
50/60
Hz
Rating
50/60
Hz
Rating
50/60
Hz
Rating
50/60
Hz
Rating
50/60
Hz
kVA
kW
675
675
750
750
825
825
900
900
1000
1000
1100
1100
Input and Output Voltage
Volts
380/380
380/380
380/380
380/380
380/380
380/380
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
A
Amps
1200
1363
1500
1600
1818
2000
AWG or
kcmil
(each)
500
(5)
500
(6)
500
(6)
500
(6)
500
(8)
500
(8)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
1026
1139
1253
1367
1519
1671
Minimum Conductor Size
Number per Phase
AWG or
kcmil
(each)
500
(5)
500
(5)
500
(5)
500
(6)
500
(6)
500
(8)
DC Input from Each Battery Disconnect to Each UPS UPM
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
C
Amps
per
UPM
603
603
603
603
603
603
AWG or
kcmil
(each)
500
(3)
500
(3)
500
(3)
500
(3)
500
(3)
500
(3)
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps
1026
1139
1253
1367
1519
1671
Minimum Conductor Size
Number per Phase
AWG or
kcmil
(each)
500
(5)
500
(5)
500
(5)
500
(6)
500
(6)
500
(8)
NOTE
Callout letters
A
,
B
,
C
, and
D
Terminals E1A through E5A and E9A through E11A are stud type terminals. The
intercabinet power wiring connections for this equipment are rated at 90
°
C. See
Table 3‐15 for intercabinet power cable terminations and Table 3‐16 for supplied
intercabinet wiring terminal hardware.
The torque values listed in Table 3‐15 for the M8 studs are the maximum allowable.
Tightening further will risk breaking or twisting the stud.
Figure 4‐8 through Figure 4‐11 show the location of the intercabinet power cable
terminals inside the UPS.