Table 3‐5. 480V Input/Output Ratings and External Wiring Requirements for the Four UPM – Common Battery
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
1000
1000
1100
1100
1200
1100
1200
1200
Input and Output Voltage
Volts
480/480
480/480
480/480
480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
Minimum Conductor Size
Number per Phase
A
Amps
1485
1600
1600
1781
AWG or
kcmil
(each)
500
(5)
500
(6)
500
(6)
500
(6)
AC Input to UPS Bypass
Full Load Current
(3) Phases, (1) Ground
B
Amps
1203
1323
1443
1443
Minimum Conductor Size
Number per Phase
AWG or
kcmil
(each)
500
(5)
500
(5)
500
(5)
500
(5)
DC Input from Battery Disconnect to UPS
(1) Positive, (1) Negative
Minimum Conductor Size
Number per Pole
(1) Positive, (1) Negative
C
Total
Amps
2193
2412
2412
2632
AWG or
kcmil
(each)
500
(10)
500
(12)
500
(12)
500
(12)
AC Output to Critical Load
Full Load Current
(3) Phases, (1) Ground
D
Amps
1203
1323
1443
1443
Minimum Conductor Size
Number per Phase
AWG or
kcmil
(each)
500
(5)
500
(5)
500
(5)
500
(5)
NOTE
Callout letters
A
,
B
,
C
, and
D
NOTE
Bypass wiring data is not applicable to IOM configurations.
Battery Conductor Sizing:
Eaton strongly recommends using the specified DC conductor size and quantity shown above for optimum system
performance and battery run time.
Battery Cable Routing Requirements
Conduit applications:
* Each conduit must have a Positive, Negative, and Ground conductor.
* There must be an equal number of positive and negative conductors in a single conduit. Only one ground conductor is required in each
conduit.
Raceway applications:
* Positive and negative battery cables must be run side by side in the raceway in an alternating pattern (+ - + - + - + -).
* There must be a ground cable running in the raceway with the battery cables
.