PR750LCD 

User’s Manual 

K09-0000074-00 

 

 

  (SAVE THESE INSTRUCTIONS) 

This manual contains important safety instructions. Please read and follow all instructions carefully during installation and operation of the unit. 

Read this manual thoroughly before attempting to unpack, install, or operate your UPS. 

CAUTION!   

To  prevent  the  risk  of  fire  or  electric  shock,  install  in  a  temperature  and  humidity  controlled  indoor  area  free  of  conductive 

contaminants.    (Please see specifications for acceptable temperature and humidity range). 

CAUTION!   

To  reduce  the  risk  of  electric  shock,  do  not  remove  the  cover  except  to  service  the  battery.  Turn  off  and  unplug  the  unit  before 

servicing the batteries. There are no user serviceable parts inside except for the battery. 

CAUTION!   

Hazardous live parts inside can be energized by the battery even when the AC input power is disconnected. 

CAUTION!   

The

 

UPS must be connected to an AC power outlet with fuse or circuit breaker protection.    Do not plug into an outlet that is not 

grounded.    If you need to de-energize this equipment, turn off and unplug the unit. 

CAUTION!   

To avoid electric shock, turn off the unit and unplug it from the AC power source before servicing the battery or installing a computer 

component. 

CAUTION!

    Not for use in a computer room as defined in the Standard for the Protection of Electronic Computer/Data Processing Equipment, 

ANSI/NFPA 75. 

CAUTION!

    To  reduce  the  risk  of  fire,  connect  only  to  a  circuit  provided  with  20  amperes  maximum  branch  circuit over  current  protection in 

accordance with the National Electric Code, ANSI/NFPA 70. 

DO  NOT  USE  FOR  MEDICAL  OR  LIFE  SUPPORT  EQUIPMENT!   

CyberPower  Systems  does  not  sell  products  for  life  support  or  medical 

applications.   

DO NOT

 use in any circumstance that would affect the operation and safety of life support equipment, medical applications, or 

patient care. 

DO NOT USE WITH OR NEAR AQUARIUMS!   

To reduce the risk of fire or electric shock, do not use with or near an aquarium.

   

Condensation 

from the aquarium can cause the unit to short out. 

 
 

 

 

INTRODUCTION 

Thank you for selecting a CyberPower Systems UPS product. This UPS is designed to provide unsurpassed power protection, operation and 

performance during the lifetime of the product. 

UNPACKING 

Inspect the UPS upon receipt. The box should contain the following: 

(a) UPS unit (b) User’s manual (c) Emergency Power Off cable (gray) (d) PowerPanel

®

 Business Edition software CD (e) Serial cable (f) USB 

A+B type cable (g) Warranty registration card (h) Function Setup Guide 

OVERVIEW

 

The PR750LCD UPS provides complete power protection from utility power that isn't always consistent. The PR750LCD features 1030 Joules of 

surge protection against power surges and maintenance free batteries for long lasting battery backup during power outages. In addition to 

ensuring consistent power to your computer system and the PR750LCD also includes software that will   

automatically save your open files and shutdown your computer system during a utility power loss. 

AUTOMATIC VOLTAGE REGULATOR

 

The

 

PR750LCD

 

stabilizes inconsistent utility power voltage to nominal levels that are safe for equipment.   

Inconsistent utility power may be damaging to important data files and hardware, but with   

Automatic Voltage Regulation (AVR),

 

damaging voltage levels are corrected to safe levels.    AVR   

automatically increases low utility power and decreases high utility power to a consistent and safe   

110/120 volts. 

HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT

 

1.

  Ensure that the equipment plugged into the outlets does not exceed the UPS unit’s rated capacity (750VA/525W for PR750LCD).    If the 

rated capacities of the unit are exceeded, an overload condition may occur and cause the UPS unit to shut down or the circuit breaker to trip.     

HARDWARE INSTALLATION GUIDE 

1.  Your new UPS may be used immediately upon receipt. However, to ensure the battery’s maximum   

charge capacity, it is recommended that you charge the battery for at least 8 hours. Your UPS is equipped   

with an auto-charge feature. When the UPS is plugged into an AC outlet, the battery will automatically   

charge whether the UPS is turned on or off. 

2.  Note: This UPS is designed with a safety feature to keep the system from being turned on during shipment.

 

The first time you turn the UPS on, you will need to have it connected to AC power or it will not power up.

 

3.  With the UPS unit turned off and unplugged, connect your computer, monitor, and any other

 

peripherals requiring battery backup into the 

battery power supplied outlets. 

DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump or other large 

electrical devices into the “Battery and Surge Protected Outlets”. The power demands of these devices may overload and damage 

the unit. 

4.  Plug the UPS into a 2 pole, 3 wire grounded receptacle (wall outlet).    Make sure the wall branch outlet is   

protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air   

conditioner, copier, etc…).    The warranty prohibits the use of extension cords, outlet strips, and surge strips. 

5.  Press the power switch to turn the unit on.    The Power On indicator light will illuminate and the unit will “beep”. 

If an overload is detected, an audible alarm will sound and the unit will emit one long beep.    To correct this, turn the UPS off and unplug at 

least one piece of equipment from the battery power supplied outlets.    Make sure the circuit breaker is depressed and then turn the UPS on. 

6.  To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times. 

7.  To store the UPS for an extended period, cover it and store with the battery fully charged.    While in storage, recharge the battery every three 

months to ensure battery life. 

8.  Insure the wall outlet and UPS are located near the equipment being attached for proper accessibility. 

9.  The LCD module is wall-mountable for extended distance control. Follow the steps below for installation procedure. 

a. Remove the LCD module from the front panel. 

b. Hang the LCD module on the wall. 

c. Replacing the LCD on the UPS - To place the LCD back on the UPS, roll up the LCD cable, return it to the space between the front panel &   

battery cover, and replace the LCD. 

 

 

 

 

 

 

 

 

 

 

 

 

 
 

DESCRIPTION 

 

Front Panel 

Power Switch / Power On Indicator 

Used as the master on/off switch for equipment connected to the battery power supplied outlets. 

Online Indicator 

This LED is illuminated when the utility power is normal and the UPS outlets are providing   

power, free of surges and spikes. 

On Battery Indicator 

During a severe brownout or blackout, this LED is illuminated and an alarm sounds (two   

short beeps followed by a pause) to indicate the UPS is operating from its internal batteries. 

Fault 

This LED is illuminated if there is a problem with the UPS. 

Replace Battery Indicator 

This LED is illuminated to remind users to replace the battery.

 

Status/Tab Button 

For UPS status information, press the button for 1 second. For additional information including the use of the button as a Tab, please refer 

to the 

Function Setup Guide

Setup/Enter Button 

Press the Setup button for 1 second to enter setup menu and then select the functions for configuration. For more information about the 

Setup/Enter button, please refer to the 

Function Setup Guide

Control/Up Button 

Press the Control button for 1 second to enter control menu and then select the functions for configuration. This button is also used to scroll 

up. For more information about the Control/Up button, please refer to the 

Function Setup Guide

Test/Down Button 

Press the Test switch for 1 second to enter test menu and then select the functions for configuration. This button is also used to scroll down. 

For more information about the Test/Down button, please refer to the 

Function Setup Guide

10  Logs/Esc Button 

Press the Logs button for 1 second to view the events or logs that have been recorded.   

This button is also used to exit a menu. For more information about Logs/Esc button,   

please refer to the 

Function Setup Guide

 

Rear Panel

 

Battery and Surge Protected Outlets 

The unit has six battery powered/surge suppression outlets for connected equipment to   

ensure temporary uninterrupted operation of your equipment during a power failure.   

(DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump   

pump or other large electrical devices into the “Battery and Surge Protected Outlets”.   

The power demands of these devices may overload and damage the unit.)

 

Serial/USB Ports to PC 

The Serial and USB ports allow connection and communication between the   

computer and the UPS unit. Note: Only one port can be used at a time. 

EPO Port 

Use the provided gray EPO cable to connect to a provided EPO contact switch.   

Follow the appropriate circuit diagram to the right to wire the cable to your   

EPO configuration. The EPO remote switch is a switch installed in an outside   

area, connected to the unit via the Emergency Power Off cable. In case of an   

emergency, it can be used to immediately cut-off power from the UPS. 

SNMP/HTTP Network Slot 

Remove the cover panel to install an optional RMCARD to remotely monitor   

and manage your UPS over a network. 

Circuit Breaker 

Located on the back of the UPS, the circuit breaker provides overload and fault protection. 

AC Input Power Cord 

Heavy-duty power cord. 

 

REPLACING THE BATTERY 

Replacement of batteries located in an 

OPERATOR ACCESS AREA

.   

1. 

When replacing batteries, replace with the same number of the following battery: CyberPower / RB1270X2B for the PR750LCD. 

2. 

CAUTION! 

  Risk of Energy Hazard, 12V, maximum 9 Ampere-hour battery. Before replacing batteries, remove conductive jewelry such 

as chains, wrist watches, and rings. High energy conducted through these materials could cause severe burns. 

3. 

CAUTION! 

  Do not dispose of batteries in a fire. The batteries may explode. 

4. 

CAUTION! 

  Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic. 

CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BATTERIES ACCORDING 

TO LOCAL REGULATIONS. 

 

BATTERY REPLACEMENT PROCEDURE: 

1. 

Turn off and unplug all connected equipment. 

2. 

Turn the UPS off and unplug it from the AC power source. 

3. 

Remove the front panel of the UPS. 

4. 

Pull out both round knobs and remove the battery compartment cover completely off of the unit. 

5. 

Remove the batteries from the compartment. 

6. 

Disconnect the battery wires from the batteries. 

7. 

Install the replacement batteries by connecting the wire bundle (composed of one red wire and one black wire) to the connector from the 

battery pack. 

8. 

Put the batteries back into the compartment. 

9. 

Re-install the battery compartment cover and push both round knobs back into place. 

10. 

Put the front panel back on the UPS. 

11. 

Connect to AC power and charge the new batteries for up to 16 hours to insure a full charge. 

 

 

 

 

 

 

 

 

 

 

REMINDER:   

Batteries are considered 

HAZARDOUS WASTE

 and must be disposed of properly.    Most retailers that sell lead-acid batteries 

collect used batteries for recycling, as required by local regulations. 

 

 

 

 

 

Status Menu/Switch

 

 

Operation Mode 

 

Load Power 

 

Load VA 

 

Load Amps 

 

Load Energy 

 

Estimated Runtime 

 

Battery Information 

 

Input 

 

Output 

 

Last Self Test 

 

Date & Time 

Setup Menu/Switch

 

 

Setup Wizard 

 

Utility Power 

 

MIN O/P Voltage 

 

MAX O/P Voltage 

 

LCD Auto Sleep 

 

Audible Alarm 

 

Temporarily Mute 

 

Sensitivity 

 

Low Battery Warning 

 

Auto Self Test 

 

Date & Time 

 

Battery Change Date 

 

Firmware Update 

 

Power Meter Reset 

 

Back to Default 

 

Delay Turn On 

 

Delay Turn Off 

 

Reboot Duration 

 

Minimum Restore Capacity 

 

Uptime on Battery 

 

Reserved Runtime 

Control Menu/Switch

 

 

UPS On/Off 

 

Test Menu/Switch

 

 

Self Test 

 

Alarm Test 

 

Battery Calibration 

Logs Menu/Switch

 

 

Transfer Event X1-X10 

 

Next Battery Change 

BASIC OPERATION 

INSTALLING YOUR UPS SYSTEM 

IMPORTANT SAFETY WARNINGS 

DEFINITIONS FOR ILLUMINATED LCD INDICATORS 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Reviews: