Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
35
Table 9. Separate Rectifier Input UPM Ratings and External Wiring Requirements for the Three UPM Power Xpert 9395-
825/650, 9395-825/750, and 9395-825/825 and the Two UPM Power Xpert 9395-825/450, 9395-825/500, 9395-825/550 –
Separate Battery
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
275
250
275
250
Input and Output Voltage
Volts
400
480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
453
377
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
2/0
(3)
4/0
(2)
NOTE: Callout letters
A
maps to
NOTE If a 4-pole Automatic Transfer Switch (ATS) is used to connect the UPS to a generator or alternative input source, it may
interrupt the UPS input neutral during its transition between sources. For the 9395 UPS:
The ATS transition must be open in both directions. The "break" time for the contacts must be at least 50 ms. This allows the UPS to
operate properly,
however it is important to evaluate whether the critical load will function properly as its neutral reference is rapidly
(50 ms) switched. Note also that if the UPS load is on bypass, an ATS switchover with interruption of the neutral, will interrupt the
return current path and cause a loss of all phase-to-neutral loads.
If an overlapping neutral or make-before-break ATS switch is used, the neutrals must overlap for a minimum of 50 ms during the
transition.
Table 10. Neutral Bonding Jumper Wire Size (Four Wire Only - All Ratings)
Neutral Bonding Jumper (Four Wire Output Only)
AWG or kcmil
(each)
4/0
(1)
Minimum Conductor Size Number
Terminals E1A through E5A and E9A through E12A are stud type terminals. The intercabinet power wiring
connections for this equipment are rated at 90ºC. See
for external power cable terminations,
for supplied external wiring terminal hardware.
The torque values listed in
for the M8 studs are the maximum allowable. Tightening further will risk
breaking or twisting the stud.
and
show the location of the power cable terminals inside the UPS.
Summary of Contents for Power Xpert 9395
Page 8: ......