Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
Table 6. Input/Output Ratings and External Wiring Requirements for the Three UPM Power Xpert 9395-825/650, 9395-825/
750, and 9395-825/ 825 – Separate Battery
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
650
592
650
592
750
683
750
683
825
751
825
751
Input and Output Voltage
Volts
400/400 480/480 400/400 480/480 400/400 480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
1070
892
1234
1029
1358
1132
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
500
(3)
500
(4)
500
(4)
500
(5)
500
(4)
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
B
Amps
938
782
1083
902
1191
992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
500
(3)
500
(4)
500
(3)
500
(4)
500
(4)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
938
782
1083
902
1191
992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
400
(4)
500
(3)
500
(4)
500
(4)
500
(5)
500
(5)
DC Input from Each Battery Disconnect to
Each UPS UPM
(1) Positive, (1) Negative
C
Amps per UPM
551
551
551
551
551
551
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
250
(3)
250
(3)
250
(3)
250
(3)
250
(3)
250
(3)
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps
938
782
1083
902
1191
992
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(3)
350
(3)
500
(4)
500
(5)
500
(4)
500
(4)