Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
243
C
Chhaapptteerr 1100 P
Prroodduucctt S
Sppeecciiffiiccaattiioonnss
1100..11
M
Mooddeell N
Nuum
mbbeerrss
The UPS is housed in a free–standing cabinet with safety shields behind the door and front panels. The UPS is
available in 50 or 60 Hz with various output power ratings.
Models
Power Rating
Frequency
Power Xpert 9395-825/650 (three UPM)
650 kVA
50/60 Hz
Power Xpert 9395-825/750 (three UPM)
750 kVA
50/60 Hz
Power Xpert 9395-825/825 (three UPM)
825 kVA
50/60 Hz
Power Xpert 9395-825/450 (two UPM)
450 kVA
50/60 Hz
Power Xpert 9395-825/500 (two UPM)
500 kVA
50/60 Hz
Power Xpert 9395-825/550 (two UPM)
550 kVA
50/60 Hz
1100..22
S
Sppeecciiffiiccaattiioonnss
1100..22..11 U
UP
PS
S IInnppuutt
The following sections detail the input, output, battery, and environmental specifications for the UPS.
Operating Input Voltage
400 Vac 480 Vac
Operating Input Frequency Range
50/60 Hz
Operating Input Current
See
,
or
Reduced for Generator
Adjustable
Input Current Harmonic Content
5% THD at full load
Power Factor
Minimum 0.99
Line Surges
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801
4
Battery Voltage
480 Vdc
Battery Charging Capacity
Configurable per UPM at nominal line voltage:
Up to 120A
Battery Shunt Trip
48 Vdc
Summary of Contents for Power Xpert 9395