Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
Table 7. Input/Output Ratings and External Wiring Requirements for the Two UPM Power Xpert 9395-825/450, 9395-825/
500, and 9395-825/ 550– Common Battery
Basic Unit Rating
Units
Rating 50/60 Hz
kVA
kW
450
410
450
410
500
455
500
455
550
501
550
501
Input and Output Voltage
Volts
400/400 480/480 400/400 480/480 400/400 480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps
741
617
823
686
905
754
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
500
(4)
500
(5)
500
(4)
500
(5)
500
(4)
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
B
Amps
650
541
722
601
794
662
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps
650
541
722
601
794
662
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(5)
DC Input from Each Battery Disconnect to
Each UPS
(1) Positive, (1) Negative
C
Total Amps
902
902
1002
1002
1103
1103
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(6)
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps
650
541
722
601
794
662
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
500
(4)