Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
161
Table 33. Display Menu Operation (Continued)
Function
Subfunction
Operation
System Setup screen to display the Storm Detection Timer screen. Use the up
or down arrow pushbutton to set the time. Press
SAVE
or
ABORT
. Once the
action is completed, the Energy Saver System Setup screen is displayed.
High Alert Timer
The High Alert Timer screen sets the length of time the UPS remains in Online
mode before transferring back to Energy Saver System mode. The time can be
set in 10 minute increments from 0 to 990 minutes. Select
HIGH ALERT
TIMER
from the Energy Saver System Setup screen to display the High Alert
Timer screen. Use the up or down arrow pushbutton to set the time. Press
SAVE
or
ABORT
. Once the action is completed, the Energy Saver System
Setup screen is displayed.
Variable Module
Management System
The Module Management System Setup screen allows the Variable Module
Management System function to be configured. Select
MODULE
MANAGEMENT SYSTEM SETUP
from the System Setup Level 0 menu to
display the Module Management System Setup screen. Use the up or down
arrow pushbutton to highlight the desired function, then press the
SELECT
pushbutton. To return to the System Setup screen, press the
ESC
pushbutton.
VMMS Load Limit
The VMMS Load Limit screen sets the maximum load that can be drawn from
a UPM before additional UPMs are activated. Select
APM LOAD LIMIT
from
the Module Management System Setup screen to display the VMMS Load
Limit screen. Use the up or down arrow pushbutton to set the load limit. Press
SAVE
or
ABORT
. Once the action is completed, the Module Management
System screen is displayed.
VMMS UPM Redundancy
The VMMS UPM Redundancy screen sets the number of UPMs to remain
active to maintain redundancy. Select
VMMS UPM REDUNDANCY
from the
Module Management System Setup screen to display the VMMS UPM
Redundancy screen. Use the up or down arrow pushbutton to set the number
of UPMs. Press
SAVE
or
ABORT
. Once the action is completed, the Module
Management System Setup screen is displayed.
High Alert Timer
The High Alert Timer screen sets the length of time the all UPMs remain
active before transferring back to Variable Module Management System
mode. The time can be set in 10 minute increments from 0 to 990 minutes.
Select
HIGH ALERT TIMER
from the Module Management System Setup
screen to display the High Alert Timer screen. Use the up or down arrow
pushbutton to set the time. Press
SAVE
or
ABORT
. Once the action is
completed, the Module Management System Setup screen is displayed.
System Level 1 Setup
Password
The System Setup Level 1 screen can be used to set the UPS date and time,
set the serial ports, change the Level 1 password, and log out of Level 1. In
addition, the Level 0 functions are available. A password is required to access
the Level 1 functions. To enter the password, select
ENTER PASSWORD
from the System Setup Level 0 menu to display the Enter Password screen.
Use the left or right arrow pushbutton to select the password character
position. Use the up or down arrow pushbutton to change the password
character. Once the password is entered, press the
DONE
pushbutton. The
System Setup Level 1 menu screen is displayed. The default password is L1.
Function Selection
Use the up or down arrow pushbutton to highlight the setup function screen
desired, then press the
SELECT
pushbutton to display the function screen.
The Level 1 screen times out after 60 minutes or can be logged out at any
time by selecting the
LOG OUT
function from the menu screen.