Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
159
Table 33. Display Menu Operation
Function
Subfunction
Operation
Events
Press the
EVENTS
pushbutton on the main menu bar or History menu bar to
display a listing of all system events that are currently active. The most recent
event is listed first. As events clear, they are removed from the Active System
Events listing. To scroll through the events, press the up or down arrow
pushbutton on the menu bar.
User History
Press the
HISTORY
pushbutton on the Active Events menu bar to display the
User History Log. The User History Log lists up to 2048 events in chronological
order, with the most recent event listed last (once 2048 is reached, the
earliest event is overwritten). The end of the log (the most recent events) is
displayed first; scroll upward to view older event listings. To scroll through the
events, press the up or down arrow pushbutton on the menu bar. To return to
the Active Events screen, press the
EVENTS
pushbutton on the menu bar.
Service History
The Service History Log is for service personnel and is password protected. If
the customer needs access to the log, contact an Eaton service representative.
Press the
SERVICE
pushbutton on the User History menu bar to display the
Service History Log. The Service History Log lists up to 2048 events in
chronological order, with the most recent event listed last (once 2048 is
reached, the earliest event is overwritten). The end of the log (the most recent
events) is displayed first; scroll upward to view older event listings. To scroll
through the events, press the up or down arrow pushbutton on the menu bar.
To return to the User History screen, press the
USER
pushbutton on the menu
bar. To return to the Active Events screen, press the
EVENTS
pushbutton on
the menu bar.
Meters UPS
Meters UPM
The Meter screens show the UPS meter readings for the unit. The default
voltage displayed on these screens is phase-to-neutral. However, an
authorized Eaton Customer Service Engineer can change the screens to
display the voltage phase-to-phase (A-B, B-C, C-A). Press the
METERS
pushbutton on the main menu bar to display the Meter screens. To scroll
through the meter screens, press the up or down arrow pushbutton on the
menu bar. The current UPS readings are displayed in the information area of
the screen.
Output – UPS
Output – UPM
The Output screen shows output voltage (phase to neutral), output current
(each phase), and frequency being supplied by the UPS, as well as the kVA,
kW, and power factor measurements.
Input – UPS
Input – UPM
The Input screen shows input voltage (phase to neutral), input current (each
phase), and frequency of the incoming utility source, as well as the kVA, kW,
and power factor measurements.
Bypass
The Bypass screen shows the bypass input voltage (phase to neutral), input
current (each phase), and frequency of the incoming utility source, as well as
the kVA, kW, and power factor measurements.
Battery – UPS
Battery – UPM
The Battery screen displays the battery voltage (Vdc), the battery current (Idc),
the minutes of battery time remaining, and battery temperature. Battery
temperature must be set up by an authorized Eaton Customer Service
Engineer. When battery life decreases to less than 20%, Check Battery is
displayed.
Statistics
The Statistics screen displays the hours on line and the total kW hours used.