157
Figure 102. Parts of the LCD
METERS
P
U
T
E
S
S
T
N
E
V
E
ALARM:
INPUT AC UNDER VOLTAGE
OUTPUT
BATT
UPS
INPUT
STSW
A
B
C
D
CONTROLS
LOAD OFF
BYPASS
A
The
UPS status
area automatically scrolls between the Eaton model number, current date and time, active alarms, active
notices, and load percent and battery runtime for the UPS. If the Environmental Monitoring Probe is installed, the
temperature and humidity sensed by the probe will also be displayed. The top line of display blinks while scrolling when the
system needs attention. Some notices and alarms may be accompanied by an audible horn. To silence the horn, press any
control panel pushbutton once. Shown is a typical alarm message. For more information about alarms and notices, see
paragraph
B
The
information area
contains data about UPS status and operations.
C
The
menu bar
lists the titles of the available screens. To select a screen, press the pushbutton underneath the desired
screen.
D
The
navigation pushbuttons
function depending on the screen displayed. Use the pushbuttons to select menu screens or
scroll through available screens. The LCD options above the pushbuttons indicate each pushbutton's function.
You can use the LCD and the pushbuttons to:
•
Look at a log of UPS events (alarms, notices, and commands) (see paragraph
).
•
Monitor UPS operation (see paragraph
•
Set UPS parameters (see paragraph
•
Control UPS operation (see paragraphs
System Status Screen and Controls
and
)
After approximately 30 minutes, the display screen darkens. To restore the screen, press any pushbutton
once.
77..22..44
U
Ussiinngg tthhee M
Meennuu
The UPS menu bar allows you to display data in the information area to help you monitor and control UPS
operation.
shows the basic menu structure.