196
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
5.
Press the
SELECT
pushbutton on the Charger Command menu bar.
To turn the battery charger off:
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
CHARGER
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Charger Control Command screen
is displayed.
4.
On the Charger Control Command screen, select
CHARGER OFF
.
5.
Press the
SELECT
pushbutton on the Charger Command menu bar.
77..44..2277 U
Ussiinngg tthhee U
UP
PS
S LLO
OA
AD
D O
OFFFF P
Puusshhbbuuttttoonn oorr C
Coom
mm
maanndd
A UPS Load Off is initiated by the
LOAD OFF
pushbutton from the main menu bar, the Load Off command on
the UPS Control Command screen, or the Load Off command on the Bypass Control Command screen. The
UPS
LOAD OFF
controls the UPSs' outputs by powering down the UPS and de–energizing the critical load.
NOTE
The UPS Load Off controls each UPS independently and does not shut down the whole
distributed bypass system unless all UPSs have been transferred to bypass. To
immediately shut down the whole system, use the REPO switch (see paragraph
Using the Remote Emergency Power-off Switch
).
To use the
LOAD OFF
pushbutton:
1.
Press the
LOAD OFF
pushbutton on the UPS to shut down.
The Load Off screen is displayed, providing a choice to proceed or abort the shutdown.
All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this
feature only when you want to de–energize the critical load.
2.
To shut down the UPS, press
LOAD OFF
from the Load Off menu bar, and hold for three seconds. To
abort the shutdown, press
CANCEL
.
When LOAD OFF pushbutton is selected and held for three seconds, the input, output, battery, and
bypass backfeed contactors open, and the power module is turned off on the UPS.
3.
If another UPS is to be shut down, proceed to that UPS and repeat Steps 1 and 2.
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identified and
cleared.
4.
Restart the UPS after pressing the
LOAD OFF
pushbutton by following the procedure in paragraph
Starting the Distributed Bypass System in Online Mode
or
Starting the Distributed Bypass System in Bypass Mode
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
To use the LOAD OFF command: