NOTE
The following instructions are for the Eaton-supplied REPO switch. If a customer-
supplied REPO switch is used, it may not activate in the same manner; refer to the
operating instructions provided with the switch.
To use the REPO switch:
1.
Firmly push the red pushbutton until it locks into place. The switch latches into the activated state (see
The input, output, and bypass backfeed contactors open, the battery breaker or disconnect is tripped, and
the power module is turned off immediately, without asking for verification.
Do not attempt to restart the system after the REPO until the cause of the shutdown has been identified and
cleared.
2.
To deactivate the REPO switch in preparation for restarting the UPS, insert the supplied key and rotate
clockwise until the red pushbutton releases (see
). To remove the key, rotate the key back to
the vertical position.
3.
Restart the UPS by following the procedure in paragraph
Starting the UPS in Online Mode
or
Starting the UPS in Bypass Mode
.
Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.
Figure 106. REPO Operation
Deactivated
Unlock pushbutton to release
Activated
Pushbutton locked into place
77..44
M
Muullttiippllee U
UP
PS
S D
Diissttrriibbuutteedd B
Byyppaassss O
Oppeerraattiioonn
The paragraphs in this section provide operating instructions for a UPS system containing multiple UPSs.
NOTE
A Field Installed UPM (FI-UPM) is always designated as UPM 4.
77..44..11
S
Sttaarrttiinngg tthhee D
Diissttrriibbuutteedd B
Byyppaassss S
Syysstteem
m iinn O
Onnlliinnee M
Mooddee
To start the distributed bypass system:
1.
Unfasten the front door latches and swing the doors open on all of the UPSs (see