170
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
12. On the Bypass Control Command screen, select
GO TO BYPASS
.
13. Press the
SELECT
pushbutton on the Bypass Command menu bar.
The critical load is immediately supplied by the bypass source, in Bypass mode.
The
BYPASS
status indicator is illuminated. The Bypass status indicates
ON
. The UPM status indicates
SHUTDOWN, CLOSE BATTERY
.
77..33..99
EEnnaabbllee EEnneerrggyy S
Saavveerr S
Syysstteem
m M
Mooddee ffrroom
m tthhee B
Byyppaassss C
Coom
mm
maanndd M
Meennuu
To enable Energy Saver System mode:
NOTE 1
The Energy Saver System mode commands are displayed only if enabled at the factory
or by an Eaton Customer Service Engineer.
NOTE 2
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Variable Module Management System mode is enabled, the
Energy Saver System mode commands will not be displayed.
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The UPS Control Command screen is
displayed.
4.
On the UPS Control Command screen, select
ENABLE ENERGY SAVER
.
5.
Press the
SELECT
pushbutton on the UPS Command menu bar.
If the UPS is online, the UPS transfers to Energy Saver System mode.
The Online status indicator is illuminated. The UPS status indicates
ONLINE WITH ESS
. The UPM status
indicates
ONLINE
. If the battery is not charging, the power module is off.
77..33..1100 D
Diissaabbllee EEnneerrggyy S
Saavveerr S
Syysstteem
m M
Mooddee ffrroom
m tthhee B
Byyppaassss C
Coom
mm
maanndd M
Meennuu
To disable Energy Saver System mode:
NOTE 1
The Energy Saver System mode commands are displayed only if enabled at the factory
or by an Eaton Customer Service Engineer.
NOTE 2
The Variable Module Management System and Energy Saver System modes are
mutually exclusive. If the Variable Module Management System mode is enabled, the
Energy Saver System mode commands will not be displayed.
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status screen is displayed.
2.
On the System Status screen, select the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass Control Command screen
is displayed.
4.
On the Bypass Control Command screen, select
DISABLE ENERGY SAVER
.
5.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
If the UPS is online, the UPS transfers to Battery mode and then to Online mode.
The
Online
status indicator is illuminated. The UPS status indicates
ONLINE
. The UPM status indicates
ONLINE
.