36
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
Table 11. UPS Intercabinet Power Cable Terminations for the Three UPM Power Xpert 9395-825/650, 9395-825/750, and
9395-825/825 and the Two UPM Power Xpert 9395-825/450, 9395-825/500, 9395-825/550
Terminal Function
Terminal
Function
Bus Landings
Tightening
Torque Nm (lb ft)
Stud
AC Input to UPM Section
E1A (UPM 1)
E1A (UPM 2)
E1A (UPM 3)
E1A (UPM 4)
Phase A
3 – stud mounting
14.2 (10.4)
M8
E2A (UPM 1)
E2A (UPM 2)
E2A (UPM 3)
E2A (UPM 4)
Phase B
3 – stud mounting
14.2 (10.4)
M8
E3A (UPM 1)
E3A (UPM 2)
E3A (UPM 3)
E3A (UPM 4)
Phase C
3 – stud mounting
14.2 (10.4)
M8
AC Output to UPM Section
E9A (UPM 1)
E9A (UPM 2)
E9A (UPM 3)
Phase A
3 – stud mounting
14.2 (10.4)
M8
E10A (UPM 1)
E10A (UPM 2)
E10A (UPM 3)
Phase B
3 – stud mounting
14.2 (10.4)
M8
E11A (UPM 1)
E11A (UPM 2)
E11A (UPM 3)
Phase C
3 – stud mounting
14.2 (10.4)
M8
E12A (UPM 1)
E12A (UPM 2)
E12A (UPM 3)
Neutral
3 – stud mounting
14.2 (10.4)
M8
DC Input to UPM Section
1E4A (UPM 1)
2E4A (UPM
2)
3E4A (UPM 3)
Positive
6 – stud mounting
(2 per UPM)
14.2 (10.4)
M8
1E5A (UPM 1)
2E5A (UPM
2)
3E5A (UPM 3)
Negative
6 – stud mounting
(2 per UPM)
14.2 (10.4)
M8
Table 12. Supplied Wiring Terminal Hardware
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Flat Washer
M8
36
UPM AC Input, UPM Battery Input, UPM AC Output, and
Neutral
180500036-080
Conical Washer
M8
36
UPM AC Input, UPM Battery Input, UPM AC Output, and
Neutral
180500037-080
Nut
M8
36
UPM AC Input, UPM Battery Input, UPM AC Output, and
Neutral
180200001-05
For a UPS with common rectifier input terminals, E1 through E12 are 2-hole bus bar mountings for standard
NEMA 2-hole barrel lugs. The power wiring connections for this equipment are rated at 90º C. See
for