Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
37
external power cable terminations,
for supplied external wiring terminal hardware, and
for
recommended installation parts and tools not supplied by Eaton Corporation.
For a UPS with separate rectifier input terminals for the UPMs, E1 through E3 are pressure terminations, UL
and CSA rated at 90º C. See
for power cable terminations.
shows the location of the power cable terminals inside the UPS.
Table 13. UPS External Power Cable Terminations for the Three UPM Power Xpert 9395-825/650, 9395-825/750, and 9395-
825/825 and the Two UPM Power Xpert 9395-825/450, 9395-825/500, 9395-825/550
Terminal Function
Terminal
Function
Bus Landings
Tightening Torque
Nm (lb ft)
Bolt
Size
AC Input to UPS Rectifier
E1
Phase A
4 – 2 bolt mounting
76 (56)
M12
E2
Phase B
4 – 2 bolt mounting
76 (56)
M12
E3
Phase C
4 – 2 bolt mounting
76 (56)
M12
AC Input to Bypass
E6
Phase A
6 – 2 bolt mounting
76 (56)
M12
E7
Phase B
6 – 2 bolt mounting
76 (56)
M12
E8
Phase C
6 – 2 bolt mounting
76 (56)
M12
AC Output to Critical Load
E9
Phase A
6 – 2 bolt mounting
76 (56)
M12
E10
Phase B
6 – 2 bolt mounting
76 (56)
M12
E11
Phase C
6 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS –
Common Battery
E4
Battery (+)
8 – 2 bolt mounting (2 UPM)
12 – 2 bolt mounting (3 UPM)
16 – 2 bolt mounting (4 UPM)
76 (56)
M12
E5
Battery (-)
8 – 2 bolt mounting (2 UPM)
12 – 2 bolt mounting (3 UPM)
16 – 2 bolt mounting (4 UPM)
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS –
Separate Battery (UPM 1)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS –
Separate Battery (UPM 2)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS –
Separate Battery (UPM 3)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
DC Input from Battery or
Battery Disconnect to UPS –
Separate Battery (UPM 4 FI-
UPM)
E4
Battery (+)
4 – 2 bolt mounting
76 (56)
M12
E5
Battery (-)
4 – 2 bolt mounting
76 (56)
M12
Input and Output Neutral
E12
Neutral
12 – 2 bolt mounting
22 (16)
M10
Customer Ground
Ground
Ground
15 – 1 bolt mounting
22 (16)
M10
NOTE Customer ground, sized in accordance with NEC Table 250.122, can be run in any conduit listed in
NOTE Bypass terminations are not applicable to IOM configurations.
Table 14. Supplied External Wiring Terminal Hardware Kit
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Bolt, Grade 5
M10 x 25 mm
15
Ground
180190078-087
Bolt, Grade 5
M12 x 45 mm
92
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180190078-113
Summary of Contents for Power Xpert 9395
Page 8: ......
Page 269: ...16420172515 164201725 15 ...