38
Eaton Power Xpert 9395 UPS Installation and Operation Manual 164201725—Rev 15
Table 14. Supplied External Wiring Terminal Hardware Kit (Continued)
Part
Size
Quantity
Terminals Used On
Eaton Part Number
Flat Washer
M10
15
Ground
180500036-100
Flat Washer
M12
184
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180500036-120
Conical Washer
M10
15
Ground
180500037-100
Conical Washer
M12
92
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180500037-120
Nut
M12
92
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180200001-07
NOTE Bypass terminations are not applicable to IOM configurations.
Table 15. Recommended Installation Parts and Tools (Not Supplied by Eaton)
Part
Size
Quantity
Manufacturer
Part Number
Notes
Long Barrel 2-Hole Lug
2/0 AWG
As required
Thomas & Betts
54862BE
Copper wire only
3/0 AWG
Thomas & Betts
54864BE
4/0 AWG
Thomas & Betts
54866BE
250 MCM
Thomas & Betts
54868BE
300 MCM
Thomas & Betts
54870BE
350 MCM
Thomas & Betts
54872BE
400 MCM
Thomas & Betts
54874BE
500 MCM
Thomas & Betts
54876BE
Manual Hydraulic Crimp Tool
14 Ton
1
Thomas & Betts
TBM14M
Die Set
N/A
1
Thomas & Betts
15506
Table 16. Separate Rectifier Input UPM Power Cable Terminations for the Power Xpert 9395-275/225, 9395-275/275, and
9395-250/228
Terminal Function
Terminal
Function
Size of Pressure
Termination
Tightening Torque
Nm (lb ft)
Type Screw
AC Input to each UPM
Rectifier
E1
Phase A
2 - #6-250 kcmil
42.4 (375)
5/16” Hex
E2
Phase B
2 - #6-250 kcmil
42.4 (375)
5/16” Hex
E3
Phase C
2 - #6-250 kcmil
42.4 (375)
5/16” Hex
Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See
for conduit
requirements.
Per NEC article 300, 3(B)(1), all three-phase conductors must be run in the same conduit. Neutral and ground
must be run in the same conduit as the phase conductors.
Conduit is sized to accommodate one neutral conductor the same size as the phase conductor and one ground
conductor sized in accordance with NEC Table 250.122.
Conduit sizes listed are for copper wiring only.