www.eaton.com
Network
Management Card
(Network-MS)
User Manual
Network Management Card
– User Manual
34003991XT_EN/JC
Page
63/143
4.4.6 Central shutdown configuration
Note: Intelligent Power® Manager provides more advanced configuration management features
Click on Notified Applications in the menu, then Configuration.
This page is used to define either the "shutdown" or the "notification" settings used by the Intelligent Power
Protector that connects to Network Management Card. These settings are used by the Intelligent Power Protector
if they are in central-configuration mode or if their configuration is not valid.
•
Shutdown duration
: the shutdown duration necessary to properly shutdown the computer.
•
Shutdown after
: the time available to the user from the power failure until the launch of the shutoff
sequence of the UPS and equipment. This parameter is optional. Uncheck the box if you wish not to use
this parameter.
•
Broadcast
: Sends network notifications to the
Administrators
and
Users
groups on events declared in
the server hosting the NSM
If you wish to set up a new configuration for the Network Shutdown Modules already set to "central-configuration
mode", proceed as follows:
•
Change the IPP parameters in the "Notified Applications" page.
•
Click the "Save" button.
•
In this page, select the IPPs for which you want to apply the new configuration.
•
Press the "Remove" button.
•
The IPPs selected will disconnect then reconnect and use the new configuration.