www.eaton.com
Network
Management Card
(Network-MS)
User Manual
Network Management Card
– User Manual
34003991XT_EN/JC
Page
79/143
5.1.2 Controlled outlets
Certain UPS models are equipped with controlled outlets (generally 2) which are always dependant on the UPS's
main outlet.
Shutdown of the main outlet systematically causes shutdown of the programmable outlets.
Warning: Some inverters have only 2 programmable plugs without mains plug (Powerware). With this type of
UPS, stopping a programmable outlet causes the UPS shutdown.
The following notations are used to identify these outlets:
•
Main outlet:
Main
•
Controlled outlet 1
1
•
Controlled outlet 2
2
Start shutdown main
output
Shutdown duration
main output
Utility failure
Shutdown duration 1
Shutdown
duration 2
Shutdown duration 3
Utility
Main output
NSM 1 on main
output
NSM 2 on outlet 1
NSM 3 on main
output
Shutdown after:
Utility restore
Start shutdown
outlet 1
Shutdown
duration outlet
1
Outlet 1
5.1.3 Protection of a server connected to a controlled outlet
Intelligent Power Protector (IPP) starting with version 3.0 are compatible with the controlled outlets.
After connecting the server electrically to one of the controlled outlets, the IPP must be informed of the outlet
number to which it is connected.
Refer to the documentation of the IPP available on the internet site
www.eaton.com
5.1.3.1 Load shedding or sequential shutdown
It is possible to optimise backup time by shutting down non-priority equipment or sequencing the shutdown of
several devices.