www.eaton.com
Network
Management Card
(Network-MS)
User Manual
Network Management Card
– User Manual
34003991XT_EN/JC
Page
61/143
•
Application Name
: Given by the application at subscription time.
•
Output
: number of the UPS output from which the client is powered.
•
Configuration
: shows where the parameters of the Intelligent Power Protector come from: Local
(coming from the application) or Central (coming from the card).
The
Central shutdown configuration
is available by clicking on the
Configuration
link.
•
Shutdown duration
: the shutdown duration necessary to properly shutdown the computer.
•
Shutdown after
: the time available to the user from the power failure until the launch of the shutoff
sequence of the UPS and equipment.
•
Connected
: This value is set to YES if the notified application connects through TCP protocol.
Many actions are available on this page:
•
Remove
: Depending on the kind of application, the selected ones will definitively disappear from the
table as SNMP applications, or they will disappear and automatically re-subscribe as Intelligent Power
Protector applications.
•
Utility failure Test
: Two alarms, 'Utility failure' and 'Utility restored' spaced 60 seconds apart, will be sent
to the applications selected, making sure that the applications can be reached over the network.
•
Shutdown Test
: This test simulates a UPS low battery sequence. It enables an easy check to see if the
server protection works correctly.
- No intervention on the UPS is required.
- The applications selected will process the simultaneous alarms and perform an actual shutdown
sequence.
WARNING!
- This test will generate a REAL shutdown sequence of the selected servers on which the Intelligent Power
Protector application is running.
•
Add NMS
: allows an SNMP trap receiver to be added such as a Network Management System.
•
Modify NMS
: allows an SNMP trap receiver to be modified.
Both buttons open a new window where it is possible to enter the Application name, the Hostname or IP
Address, the trap port, the protocol version needed: V1, V3 or both, the Trap community (only used in
V1) and the filter on the several implemented MIBs.