www.eaton.com
Network
Management Card
(Network-MS)
User Manual
Network Management Card
– User Manual
34003991XT_EN/JC
Page
116/143
HighNotify
LowNotify
HighShutdown
LowShutdown
Examples
#> getHum Offset
Comments
6.4.9.6 “setHum”
Purpose
To modify a humidity setting
Syntax
setHum [option1] [option2] ...
options :
HighThreshold = xx
LowThreshold =xx
Hysteresis = xx (0..5)
Offset = xx (-5..5)
HighNotify = 0|1 (0=No, 1=Yes)
LowNotify = 0|1 (0=No, 1=Yes)
HighShutdown = 0|1 (0=No, 1=Yes)
(1)
LowShutdown = 0|1 (0=No, 1=Yes)
(1)
Examples
#> setHum HighNotify=0
Comments
(1)
: Writing enabled only if the notification is enabled
6.4.9.7 “getInput1” or “getInput2”
Purpose
To read input setting
Syntax
getInput1 [option1] [option2] ...
options :
iName
State[0].Description
State[0].Notify
State[0].Shutdown
State[1].Description
State[1].Notify
State[1].Shutdown
Examples
#> getInput1 iName
Comments
6.4.9.8 “setInput1” or “setInput2”
Purpose
To modify input setting
Syntax
setInput1 [option1] [option2] ...
options :