www.eaton.com
Network
Management Card
(Network-MS)
User Manual
Network Management Card
– User Manual
34003991XT_EN/JC
Page
11/143
NMC also supplies alarms to the Intelligent Power Protector in order to trigger shutdowns or manage other
automatic actions on protected servers.
1.2.2 Direct sending of E-mail
When a UPS event occurs, the Network Management Card can directly notify up to 4 addresses by e-mail. (see
E-mail Notification and
E-mail message settings
)
1.2.3 Sending text messages (SMS)
SMS notification requires the use of a third-party application that converts emails to SMS. The card offers the
possibility of redirecting UPS alarms to an e-mail server. The format of these e-mails is compatible with mobile
telephone e-mail/SMS transfer systems proposed by ISPs. The format to be used depends on the service
provider.
1.2.4 Compatibility with the Network Management Systems (NMS) – Trap sending
The Network Management Cards are compatible with the major Network Management Systems (IBM Tivoli, CA
Unicenter, HP Insight Manager). The Software Suite offering includes the necessary SNMP plug-ins to allow an
easy integration in the NMS. Events are notified by SNMP trap.
•
NMS can subscribe on page
“
Notified Applications
”
•
The trap list is given in the
appendix
.
1.2.5 Environment Sensor (option)
The optional
Environment Sensor
(EMP) solution can be connected to the Card Settings port of the
Network Management Cards.
Environment Sensor enables measurement of temperature and humidity around the UPS, allows managing
external alarms via 2 dry contacts and notification of alarms according to pre-programmed thresholds. (see
Environment Status
and
Environment Configuration
)