RECTIFIERS
The EC500 Controller supports the following Eaton rectifiers:
HPR48-ES
3kW
LPR48-ES
1.2kW
The Controller supports only one series of rectifiers in one system. Please refer to System Configuration for
Rectifier Type selection. Solar Charger is always supported irrespective of the type of rectifier selected.
Configuration 1P-N:
In this configuration all Rectifiers operates on a single phase and neutral. If system does not have any input
measurement unit (ACIF or HVLV) then Rectifiers can provide ac measurement with respect to Neutral.
Configuration 3P-N:
Rectifiers are equally distributed on three different phases, R-phase, Y-phase and B-phase with respect to
neutral. If the system does not have any other input ac measurement unit (ACIF or HVLV) then Rectifiers can
provide AC measurement for R-phase, Y-phase and B-phase with neutral.
Configuration 3P-P
In this configuration, the system uses Rectifiers which operates on phase to phase input. Single phase
Rectifiers cannot operate in this configuration. If the system does not have an HVLV card then rectifiers will
provide AC phase to phase measurement.
For Rectifier Type Selection see System Configurations at page 67
Following information and configurations are available for User.
Monitoring
Parameter
Description
Where to find:
Active Rectifier
Count
Total number of Rectifier installed and
communicating.
Display:
Menu>System Status>
Rectifier>General Status
Web:
Home>System Status>
Rectifier>General Status
Total Rectifier
Current
Total Rectifier Current in Amp.
Current Share
Deviation
Maximum current deviation among rectifiers or
Share factor stabilize in 1 minute
ECO Mode Status
Indicates if Energy Saving Mode is enabled or
disabled
Display:
Menu>Settings>Rectifier Settings>
Web:
Menu>Settings>Rectifier Settings
Rectifier Slot
Number
Rectifier Serial
Number
ID
Slot number allotted to this rectifier. This is allotted
as per sequence of registration and not actual
physical slot number
Production Serial Number of rectifier. Can be used
for verifying the registered slot number
15 digit Identification number of rectifier provided
by EC500
Display:
Menu>System Status>
Rectifier>Individual Rectifier
Status
Web:
Home>System Status>
Rectifier>Individual Rectifier
Status