EC500 Controller Handbook
Copyright © 2019 Eaton Corporation. All Rights Reserved.
Issue A March 2019
Page 51 of 107
Parameter
Description
Where to find:
Alarm Name
Set Alarm name for respective analogue engine
alarm output. This name will appear in alarm
windows and reported on SNMP.
Menu>Settings> Alarm
Management > Analog
Alarms
Web :
Home>Settings> Alarm
Management > Analog
Alarms
Configurator:
Home>Settings> Alarm
Management > Analog
Alarms
Alarm Severity
Alarm Severity (Critical / Major / Minor) of individual
alarm.
Enable Audible
Alarm Indication
Enable or disable the audible alarm indicator for
particular alarm.
Enable SNMP
If
Enabled,
SNMP Trap will be sent for this alarm. For
SNMPv3, alarm severity should be equal to or higher
than Trap receiver’s configured alarm severity.
See
page 86 for details.
Group Map 1
Select alarm group 1 to map. Individual alarm can be
mapped up to two alarm groups.
Group Map 2
Select alarm group 2 to map, optional. Individual
alarm can be mapped up to two alarm groups.
SMART ALARMS
EC500 provides 16 user configurable logic block. Each combinational logic block provides three inputs and two
function blocks. Each function block provides three logic functions i.e. AND, OR & XOR and two inputs. Each of
the two inputs can be inverted before presentation to function blocks. A graphical interface is provided for
selecting the inputs and functions. Alarm activation and de activation delays can be set. The output of each
logic alarm generator can be mapped to any available User alarm so that all functions available with User
alarms can be used seamlessly. A truth table for alarm helps in verifying the logic.