The Bus voltage should gradually increase to Equalize voltage with Battery current approaching 10% of the
Battery Ah. Equalization Mode-Set Log should be stored in the event log. After the completion of the full
duration, voltage should gradually decrease to float voltage and the display will show Float mode instead of
Equalization mode.
If a system is in float mode and the Start Hour is reached, Equalize should start immediately.
If a system is not in float mode and the Start Hour is reached, then the system will wait for the float mode and
then start the Equalization.
Equalize will stop if either of these conditions is true:
•
Equalize is disabled manually.
•
Maximum temperature is reached before set duration.
Enable Equalize Mode
•
Use the keypad to go Menu>Settings>Battery Settings>VRLA Charge Profile>Equalize Mode>Status.
Enter the appropriate pin then user will be able to see settable parameters.
•
Use Web page to go Menu>Settings>Battery Settings>VRLA Charge Profile>Equalize Mode>Status.
Monitoring
Parameter
Description
Where to find:
Status
Enables or Disables Equalize Mode
Display:
Menu>Settings>Battery
Settings>Charge
Profile>Equalize
Mode>Enable
Web:
Home>Settings>Battery
Settings>Charge
Profile>Equalize
Mode>Enable
Configuration
Parameter
Description
Where to find:
Status
Enables or Disables Equalize Mode
Display:
Menu>Settings>Battery
Settings>Charge Profile>Equalize
Mode
Web:
Home>Settings>Battery
Settings>Charge Profile>Equalize
Mode
Equalize Voltage
The bus voltage maintained during an Equalize cycle.
Use the value recommended by the battery
manufacturer. Controller will maintain this Equalize
voltage for battery charging if function is enabled.
Display:
Menu>Settings>Battery
Settings>Charge Profile>Equalize
Mode (Enable)
Web:
Start Hour
Hour of the day (0
–
23) when Equalization will start
after set interval time.